Preparing installation
Fig. 14: Side view of the fixing plate
Fig. 15: Top view of the fixing plate
(1)
70 plus 2 mm
(2)
60 plus 2 mm
Plate 45 x 5 x 40 mm,
(3)
EN 10025, S235 JR, hot-dip galvanized
(4)
45 plus/minus 1 mm
(5)
40 plus/minus 2 mm
(6)
80 plus/minus 1.5 mm
The number and arrangement of the necessary foundation rails of the base frame are illustrated in detail in a
dimension drawing. For further information, see information drawings NXAIR, order number 110-2300.9.
24
Fig. 16: Side view of the fixing plate
(7)
30 plus/minus 1 mm
Plate 80 x 5 x 145 (160) mm,
(8)
EN 10025, S235 JR, hot-dip galvanized
(9)
145 plus/minus 2 mm
(10)
30 mm
(11)
13 mm
──
──
NXAIR /
40 kA
110-0084.9 / 15