Smartgen HEM4300 User Manual page 42

Engine controller
Table of Contents

Advertisement

No.
Type
18
DPF Regeneration Test Mode
19
Reserved
20
Reserved
21
Alarm Stop Inhibit
22
Reserved
23
Reserved
24
Remote Control Mode
25
External Charging Failure
26
High Temp Shutdown
27
Low OP Shutdown
28
Remote Start/Stop
29
Raise Speed
30
Drop Speed
31
Reserved
32
Simulate Stop Key
33
Simulate Start Key
34
Simulate Load Key
35
Simulate Reset Key
36
Simulate F1 Key
37
Simulate F2 key
38
Simulate F3 key
39
Simulate F4 key
40
Simulate F5 key
41
Simulate F6 key
42
Alt Config. 1 Active
43
Alt Config. 2 Active
44
Alt Config. 3 Active
45
Reserved
46
Reserved
47
Load Input
48
Reserved
49
Air Filter Block
50
Forward Rotation
51
Backward Rotation
52
Light Clamp
53
Forward Rotation Limit
54
Backward Rotation Limit
HEM4300 Engine Controller User Manual
command to ECU.
It simulates DPF regeneration request when input is active.
All shutdown alarms are inhibited except emergency stop and
over speed shutdown. (i.e. battle mode or override mode)
Controller will not start and remote start/stop can be realized
via "Remote Start/Stop Input" or RS485 communication when
input is active.
When input is active, failed to charge warning alarm occurs.
Connects to sensor digital input.
Connects to sensor digital input.
In remote control mode, when input is active, engine can start.
When input is inactive, engine will stop.
A button can be connected externally (not self-lock), manually
control speed.
An external button (unlatched) can be connected and pressed
as simulate panel key.
When input port is active, configuration is active; Different
parameters can be set for it, making convenience for users to
choose current configuration by input port.
Act between start idle and stop idle; When input is active, load
control outputs; When it is inactive, load control stops
outputting.
Air filter alarm occurs when input is active.
Forward rotation outputs when input is active.
Backward rotation outputs when input is active.
Light clamp outputs when input is active.
Forward rotation stops output when limit is active.
Backward rotation stops output when limit is active.