Smartgen HEM4300 User Manual page 26

Engine controller
Table of Contents

Advertisement

No.
Item
12
After Stop Time
Engine Setting
1
Engine Type
2
ECU Alarm Shut
3
ECU Source Address
4
Rated Speed
5
Idle Speed Set
6
Start Attempts
7
Crank Disconnect
8
Disconnect Speed
9
Disconnect OP
Overspeed
10
Warn
Overspeed
11
Shutdown
Speed
Signal
12
Loss
HEM4300 Engine Controller User Manual
Range
(0-3600)s
(0-39)
(0-1)
(0-255)
(0-6000)r/min 2000
(0-100.0)%
(1-10)times
(0-2)
(0-200)%
(0-1000)kPa
Enable
(0-1)
Set
(0-200.0)%
Return
(0-200.0)%
Delay
(0-3600)s
Enable
(0-1)
Set
(0-200.0)%
Delay
(0-3600)s
Action
(0-2)
Delay
(0-3600)s
Default
Hold" is set 0; When it is not 0, it is time
after ETS delay before complete stop.
Time from complete stop to standby
0
status.
39
Default: 39: GTSC1-PLUS.
0: Disable
0
NOTE: When engine detects red light alarm, it
will stop when it is enabled.
Source address of ECU speed control
3
communication.
Provide standard for over speed, under
speed and load speed detection.
Set value is percentage of rated speed.
40.0
Please stabilize speed to set value
when idle running is required.
Maximum start times in case of failed
start; when this number is reached,
1
controller shall issue Failed to Start
signal.
Please refer to Table 14.
There are two kinds of disconnect
conditions for engine and starter. They
2
can be used separately or together,
aiming to separate starter motor and
engine as soon as possible.
Set value is the percentage of rated
speed; when speed is above the set
24.0
value, starter shall disconnect; Please
refer to the rear installation.
When Oil Pressure is above pre-set
value, starter shall disconnect. Please
200
refer to the following installation
instruction.
1
Set value is the percentage of rated
110.0
speed; When controller detects engine
108.0
speed is above the set threshold, it
issues warning signal.
5
0
Set value is the percentage of rated
speed; When controller detects engine
114.0
speed is above the set threshold, it
2
issues shutdown alarm signal.
0
0: Warning; 1: Shutdown; 2: No Action.
5
Time from detecting speed is 0 to
Description
1: Enable