WALL LINING INSTALLATION
There are some aspects of the wall lining installation
that are critical to the safe operation of the appliance.
An air gap of at least 3 mm around the fire is critical to
IMPORTANT
the safe operation of the LS - Gas Fireplace to ensure air
flow in and around the unit.
Avoid getting plaster in the air gap around the fire edges.
ADDITIONAL NOTES:
While the fire is safe when installed with combustible wall
linings in accordance with these instructions, please be
aware that the wall will go through hot and cold cycles
and can reach temperatures of up to 80 °C. This could
impact the durability of timber or wallpaper finishes.
If screws are used (maximum length 25 mm) around the
edge, ensure they do no interfere with the working parts
of the fire (latches, IR receiver, On/Off button).
Cut-out ref.
Minimum
A
Maximum
B
C
Below is an image to highlight the position and names of the different LS - Gas Fireplace framing components.
Adjust as and where necessary, depending on the wall lining being installed.
Lining support rails
(adjustable/removable)
Finishing trim
(accessory)
Rinnai
RHFE0800F
RHFE100
816 x 566
1016 x 341
830 x 580
1030 x 355
816 x 566
1016 x 341
810 x 560
1030 x 355
Wall lining
up to edge
RHFE1500
*
1516 x 341
1530 x 355
1516 x 341
1510 x 355
28
*
*
3mm Air Gap
Wall lining
up to edge
Edges
RHFE0800F_1000_1500 IM