Heating Operation (Room Heating / Tank Heating) - Panasonic WH-ADF0309J3E5CM Service Manual

Table of Contents

Advertisement

16.2 Heating Operation (Room Heating / Tank Heating)

16.2.1
Outdoor fan control
When heating operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted
according to figure below for Heating overload control:
16.2.2
Powerful Operation 2
During cooling / heating operation, this control is to provide fast cooling / heating operation compare to normal
operation.
Operation start if all condition below are complied:
Powerful operation ON for indoor unit.
o
Not under Annual Cooling control.
o
Not in freeze / dew prevention status.
o
Not in Heat recovery mode.
o
Operation content:
Outdoor fan speed will adjust automatically.
o
Compressor frequency will adjust automatically.
o
Operation stop when comply either one of the follow conditions:
When the powerful operation is OFF for all indoor units.
o
When annual cooling control activated.
o
When freeze / dew prevention control is activated.
o
16.2.3
Heating Quiet Operation
Provide Quiet heating operation when only 1 room / 1 tank in operation.
Starting Condition.
Indoor fan speed is lower than low fan → only available for room indoor.
Quiet mode signal (Level 1, 2, 3) is set → only available for tank.
Only 1 operation indoor / tank unit.
Not initial frequency operation.
Not in any of heating overload zone.
* All condition above are satisfied.
Control Contents.
Compressor frequency and outdoor fan speed maximum limit is set.
Cancel Condition.
Indoor fan speed is higher or equal to low fan (only available for room indoor).
Quiet mode signal is cancelled (only available for tank unit).
> 1 operation room or tank unit.
During initial frequency operation.
During any of heating overload zone.
When any of above condition is satisfied.