Auto address
3
Set.
(Select the Code no. [A1] and O/D unit no.)
▲ ▼ → ► →
(Repeat)
4
Press
● After Selecting [YES], the unit restarts.
Code no.
Set the Auto address for each O/D unit no.
A1
Select the O/D unit no. (outdoor unit) for Auto address.
Attention
●
Set Auto address after all units are turned on and 90 seconds or more have passed.
●
Operate the units after Auto address is set and 90 seconds or more have passed.
Set elec. consumption
3
Set.
(Select the power supply voltage of outdoor
units.)
▲ ▼ →
4
Select [YES].
Note
●
Set the power supply voltage of outdoor units to calculate electric consumption of the Power consumption
monitor.
●
If the setting differs from the power supply voltage of outdoor units, the electric consumption value of the Power
consumption monitor will differ from the actual calculation result by a power meter.
●
Depending on the outdoor unit model, this cannot be set.
When 3-phase model connections are used for outdoor units
Power supply voltage
380 V
400 V
415 V
Setting value
220 V
230 V
240 V
Code no.
O/D unit no.
O/D unit no.
● Outdoor unit number
156