15.3 Protection Control for Heating Operation

15.3.1
Intake Air Temperature Control
Compressor will operate at limited freq., if indoor intake air temperature is 30°C or above.
15.3.2
Outdoor Air Temperature Control
The Max current value is regulated when the outdoor air temperature rise above 14°C in order to avoid
compressor overloading.
15.3.3
Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown
below.
If the heat exchanger temperature exceeds 60°C, compressor will stop.
15.3.4
Cold Draught Prevention Control
When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced.
15.3.5
Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor
and outdoor fan motor stop and Deice LED ON.
Current Regulated
14°C
Free Within Max Limit
Outdoor air temperature
OFF
60°C
Frequency Reduce
55°C
Frequency Limited
49°C
Free
Indoor Heat
Exchanger Temp.
91
12°C
52°C
46°C