Panasonic WH-ADF0309J3E5CM Service Manual page 280

Table of Contents

Advertisement

25.2.33 Outdoor High Pressure Switch Abnormal (H64 / P04 / F27)
Malfunction Decision Conditions:
During compressor stop, and outdoor high pressure switch is remain opened.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty switch.
3. Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue for 1 minute.
Troubleshooting:
Check the CN-PSW1 connector connection:
- Turn OFF the power.
- Check the connector connection.
Is the CN-PSW1 connector
connection normal?
Check the continuity of the outdoor high
pressure switch:
- Plug out outdoor high pressure switch
connector from CN-PSW1 channel.
- Measure the connector continuity.
Is there any continuity?
Caution
No
- Connector poor contact.
- Correct the connection.
Yes
- Defect in outdoor unit PCB
Yes
(main).
- Replace the outdoor unit
PCB (main).
No
- Defect in outdoor high
pressure switch.
- Replace the outdoor high
pressure switch.
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
CN-EV
CN-PSW1
WHITE
BLUE
1
6
1
2
R
R
M
ELECTRO MAGNETIC COIL
(EXPANSION VALVE)
280
FG1
G
GREEN
HIGH PRESSURE
SWITCH
(normally close)
Multimeter

Advertisement

Table of Contents
loading

This manual is also suitable for:

S-71wf3eCu-2wz71ybe5

Table of Contents