12.1.8
Test Run
12.1.8.1
Precautions
Request that the customer be present when the test run is performed.
At this time, explain the operation manual and have the customer perform the actual steps.
Check that the 230 VAC power is not connected to the inter-unit control wiring connector terminal.
* If 230 VAC is accidentally applied, the indoor unit control PCB fuse will blow in order to protect the PCB.
In this case, make the wiring correctly.
Then disconnect the 2P connectors (OC) that are connected to the indoor unit control PCB, and replace them
with 2P connectors (EMG).
If operation is still not possible after changing the brown connectors, cut the jumper on the indoor unit control
PCB.
(Be sure to turn the power OFF before performing this work.)
Be sure to set the external static pressure before performing the test run.
12.1.8.2
Test Run Procedure
Recheck the items to check before the test run.
Return the remote controller to normal control.
Address Setting
3-LINE CONNECTION
Set the remote controller to "Test run".
Can
operation be
started?
YES
OC
Jumper
(CN040, blue)
(JP040)
EMG
(CN044, brown)
(See Section 12.1.8.3)
(See 12.1.8.4, 12.1.8.5)
(See 12.1.8.7)
See "Contents of Remote Controller Switch
NO
Alarm Display" to check the system.
Regarding the alarm contents, see the
SUPPLEMENT at the end of this manual.
Check the indoor-side drainage.
119