Panasonic WH-ADF0309J3E5CM Service Manual page 18

Table of Contents

Advertisement

Item
Power Source (Phase, Voltage, Cycle)
Input Power
Maximum Input Power For Heatpump System
Starting Current
Running Current
Maximum Current For Heatpump System
Power Factor
Power factor means total figure of compressor and
outdoor fan motor.
Number of core
Power Cord
Length
Thermostat
Protection Device
Note:
** The sound pressure and sound power level is measured with distance 1.0m from the unit and height at 1.5m.
(Test carry out for cooling at ambient 35°C DB and Water Out 7°C, heating at ambient 7°C DB / 6°C WB and
water out 55°C)
*** The sound power level is measured with accordance to EN12102 under conditions of the EN14825.
Unit
Ø
V
Hz
Condition
Cooling
kW
2.09
kW
A
Condition
Cooling
A
10.1
A
Condition
Cooling
%
90
m (ft)
18
Outdoor Unit
Single
230
50
Heating
Heat Recovery
1.82
3.15
4.90
10.1
Heating
Heat Recovery
8.7
15.0
21.6
Heating
Heat Recovery
91
-
-
Electronic Control
Electronic Control
91