Indoor Unit - Panasonic WH-ADF0309J3E5CM Service Manual

Table of Contents

Advertisement

11.2

Indoor Unit

11.2.1
Select the Best Location
Before choosing the installation site, obtain user
approval.
Install the Tank Unit in indoors with frost free
weather proof location only.
Must install on a flat horizontal and solid hard
surface.
There should not be any heat source or steam
near the Tank Unit.
A place where air circulation in the room is good.
A place where drainage can be easily done (e.g.
Utility room).
A place where Tank Unit's operation noise will not
cause discomfort to the user.
A place where Tank Unit is far from door way.
A place where accessible for maintenance.
Ensure to keep minimum distance of spaces as
illustrated below from wall, ceiling, or other
obstacles.
A place where flammable gas leaking might not
occur.
Secure the Tank Unit to prevent it being knocked
over accidentally or during earthquakes.
Please avoid installations which expose the Tank Unit
to any of the following conditions:
Extraordinary environment conditions; installation
in frost or exposure to unfavorable weather
conditions.
Voltage input exceeding the specified voltage.
11.2.1.1
Required Space for Installation
(Unit : mm)
11.2.1.2
Transport and Handling
Be careful during transportating the unit so that it
is not damaged by impact.
Only remove the packaging material once it has
reached it is desired installation location.
It may need three or more people to carry out the
installation work. The weight of Tank Unit might
cause injury if carried by one person.
The Tank Unit can be transported either in vertical
or horizontal.
If it transported in horizontal, make sure Front
o
of packaging material (printed with "FRONT")
must facing upwards.
If it transported in vertical, use the hand holes
o
on sides, slide and move to the desired
location.
Fix the Adjustable Feet
installed on a uneven surface.
Hold
Hold arrow section
to slide and move
11.2.2
To Drill a Hole in the Wall and
Install a Sleeve of Piping
1. Make a Ø70 mm through hole.
2. Insert the piping sleeve to the hole.
3. Fix the bushing to the sleeve.
4. Cut the sleeve until it extrudes about 15 mm
from the wall.
When the wall is hollow, please be sure to use the sleeve
for tube assembly to prevent dangers caused by mice
biting the connection cable.
5. Finish by sealing the sleeve with putty or
caulking compound at the final stage.
Indoor
Sleeve for tube
assembly
ø70 mm through hole
60
1 , if the Tank unit
Hold
CAUTION
Wall
Outdoor
15 mm
Approx. 5 - 7 mm
Bushing for tube assemblys
Putty or caulking compound