Diagnosis display
Abnormality/Protection control
H95
Indoor/Outdoor wrong connection
Outdoor high pressure overload
protection
H98 / F95
Cooling high pressure overload
protection
H99
Indoor heat exchanger freeze prevention
F12
Pressure switch activate
F14
Outdoor compressor abnormal revolution
F15
Outdoor fan motor lock abnormality
F16
Total running current protection
Outdoor compressor overheating
F20
protection
IPM (power transistor) overheating
F22
protection
Outdoor Direct Current (DC) peak
F23
detection
F24
Refrigeration cycle abnormality
Cooling/Heating cycle changeover
F25
abnormality
F27
Pressure switch abnormality
*F29
Low Discharge Superheat
F30
Water outlet sensor 2 abnormality
F32
Abnormal Internal Thermostat
F33
Freezing of standby unit error
Outdoor air temperature sensor
F36
abnormality
Indoor water inlet temperature sensor
F37
abnormality
Outdoor discharge pipe temperature
F40
sensor abnormality
F41
PFC control
Outdoor heat exchanger temperature
F42
sensor abnormality
F43
Outdoor defrost sensor abnormality
Indoor water outlet temperature sensor
F45
abnormality
Outdoor Current Transformer open
F46
circuit
Outdoor EVA outlet temperature sensor
*F48
abnormality
Outdoor bypass outlet temperature
*F49
sensor abnormality
Note: * This error code is not applicable for this system.
Abnormality judgement
—
—
—
4 times occurrence within
30 minutes
4 times occurrence within
20 minutes
2 times occurrence within
30 minutes
3 times occurrence within
20 minutes
3 times occurrence within
30 minutes
4 times occurrence within
30 minutes
7 times occurrence
continuously
4 times occurrence within
60 minutes
4 times occurrence within
30 minutes
Continue for 1 min.
1 times occurrence within
2550 minutes
Continue for 5 sec.
Continue for 5 sec.
3 times occurrence within
40 minutes
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
4 times occurrence within
20 minutes
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
—
Continue for 5 sec.
Continue for 5 sec.
233
Primary location to verify
Indoor/Outdoor supply voltage
Outdoor high pressure sensor
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Room Air Filter dirty or air circulation
short circuit
Indoor heat exchanger
Refrigerant shortage
Pressure switch
Power transistor module faulty or
compressor lock
Outdoor fan motor lead wire &
connector
Fan motor lock or block
Excess refrigerant
Outdoor PCB
Compressor tank temperature sensor
Clogged expansion valve or strainer
Insufficient refrigerant
Outdoor PCB
Compressor
Improper heat exchange
IPM (Power transistor)
Outdoor PCB
Compressor
Insufficient refrigerant
Outdoor PCB
Valve Close
4-way valve
V-coil
Pressure switch
Discharge Temperature Sensor
Discharge Pressure Sensor
Pressure Switch
Outdoor PCB
Water outlet sensor 2 (defective or
disconnected)
Control panel PCB thermostat
Wrong wiring and connecting pipe, or
Expansion valve leakage
Outdoor air temperature sensor
(defective or disconnected)
Water inlet temperature sensor
(defective or disconnected)
Outdoor discharge pipe temperature
sensor (defective or disconnected)
Outdoor PCB
Outdoor heat exchanger temperature
sensor (defective or disconnected)
Outdoor defrost sensor (defective or
disconnected)
Water outlet temperature sensor
(defective or disconnected)
Insufficient refrigerant
Outdoor PCB
Compressor low
Outdoor EVA outlet temperature sensor
(defective or disconnected)
Outdoor bypass outlet temperature
sensor (defective or disconnected)