13.6 Connect The Cable To The Outdoor Unit

1. Remove the Particular plate from the unit by
loosening the two screws.
2. Connecting cable between all units shall be
approved polychloroprene sheathed flexible cable,
type designation 60245 IEC 57 or heavier cable.
Other detail shall refer to table below:
Cable Connection
Outdoor unit to Tank unit
Outdoor unit to Duct unit
3. Connection cable between outdoor unit and indoor unit according to the diagram as shown.
Terminals on the indoor unit
Colour of wires (Connection cable)
Terminals on the outdoor unit
4. Secure the cable onto the control board with the cable clamper.
5. Attach the particular plate back to the original position with scew.
6. For wire stripping and connection requirement, refer to the diagram below.
7. Secure the power supply cord and connecting cables onto the control board with the holder.
8. Attach the control board cover back to the original position with screw.
WIRE STRIPPING AND CONNECTING REQUIREMENT
Wire stripping
No loose strand
when inserted
This equipment must be properly earthed.
Note: Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
Connecting Cable Size
length (max)
2
4 x 4.0 mm
2
4 x 1.5 mm
TANK UNIT
DUCT UNIT
1
2
3
1
2
1
2
3
1
2
(UNIT A)
(UNITC)
Indoor/outdoor
connecting terminal
board
5 mm or more
(gap between wires)
40 m
40 m
3
3
Conductor fully
inserted
ACCEPT
171
Conductor over
Conductor not
inserted
fully inserted
PROHIBITED
PROHIBITED
Cable clamper
Screws
Particular
plate