12.1.2
Selecting the Installation Site
12.1.2.1
Indoor Unit
AVOID:
areas where leakage of flammable gas may be
expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room
directly. This may cause "condensation" on the air
discharge ports, causing them to spray or drip
water.
locations where the remote controller will be
splashed with water or affected by dampness or
humidity.
installing the remote controller behind curtains or
furniture.
locations where high-frequency emissions are
generated.
DO:
select an appropriate position from which every
corner of the room can be uniformly cooled.
select a location where the ceiling is strong
enough to support the weight of the unit.
make sure to install protective guards on the
suction and discharge side to prevent somebody
from touching the fan blades or heat exchanger.
select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
allow room for operation and maintenance as well
as unrestricted air flow around the unit.
the limitation of the tubing length between the
indoor and the outdoor units should be referred to
the Installation Instructions of the outdoor unit.
allow room for mounting the remote controller
about 1m off the floor, in an area that is not in
direct sunlight or in the flow of cool air from the
indoor unit.
< Horizontal installation >
350 mm
250 mm
* It is necessary to make space for the cleaning as
well as the maintenance of the drain pan and the
heat exchanger.
Do not put any obstacle not to cause obstructing
maintenance or cleaning works.
If the place where the ceiling material cannot be
removed, make an opening section below the bottom
surface of the indoor unit in order to take it out.
If it is impossible to provide an opening, make space
more than 300 mm between the indoor unit's bottom
surface and the ceiling material.
< Vertical installation >
250 mm
97
20 mm
650 mm
350 mm
20 mm *
650 mm
300 mm
250 mm