Panasonic WH-ADF0309J3E5CM Service Manual page 130

Table of Contents

Advertisement

12.1.10.2 Operating the High-spec Wired
Remote Controller (CZ-RTC5B)
[
]
START
How to set the external static pressure
1. Keep pressing the
simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the
LCD display.
2. Press the
or
If you wish to see the next screen instantly, press
the
or
button. Select "8. Detailed
settings" on the LCD display and press the
button.
The "Detailed settings" screen appears on the
LCD display.
Select the "Unit no." by pressing the
button for changes.
Detailed settings
Unit no.
Code no.
Sel.
Next
20:30 (THU)
,
and
buttons
20:30 (THU)
button to see each menu.
20:30 (THU)
or
20:30 (THU)
Set data
10
3. Select the "Code no." by pressing the
button.
Change the "Code no." to "B0" by pressing the
or
Detailed settings
Unit no.
1-1
Sel.
4. Select the "Set data" by pressing the
button.
Select one of the "Set data" among "0001" –
"0010" according to the desired external static
pressure setting by pressing the
button.
Then press the
(See the table below.)
When setting to auto airflow volume control:
Select the setting data to "-002".
Then press the
Table 10-2 Setting the external static pressure
Indoor unit type
S-71WF3E
Outdoor unit type
CU-2WZ71YBE5
External static pressure of the rated airflow
volume (Pa)
150
140
130
120
110
90
70
50
30 *
10
No auto airflow volume setting
Auto airflow volume setting
* Setting at shipment
130
button (or keeping it pressed).
20:30 (THU)
Code no.
Set data
-001
B0
Next
button.
button.
Item code
or
or
or
B0
0010
0009
0008
0007
0006
0005
0004
0003
0002
0001
-001
-002