SMA Solar Technology AG
Event number
Message, cause and corrective measures
6614
Overload
The device at Lxx has been loaded over its 5-minute rated capacity.
Corrective measures:
6615
Overload
The device at Lxx has been loaded over its 30-minute rated capacity.
Corrective measures:
6616
Overload
The device at Lxx has been loaded over its rated short-term capacity.
Corrective measures:
7002
Fan sensor error permanently on
7003
There is a short circuit or cable break at a temperature sensor of the device at line conductor
Lxx.
7004
Corrective measures:
7010
Short circuit battery temp. sensor > Check sensor status and function
Short circuit on battery temperature sensor
Corrective measures:
7011
Cable break battery temp. sensor > Check sensor status and function
Cable break, battery temperature sensor
Corrective measures:
7101
SD memory card defective
Micro SD card in the inverter is faulty.
Corrective measures:
Operating manual
• Reduce the power of the loads.
• Reduce the power of the loads.
• Reduce the power of the loads.
• Contact the Service.
• Ensure that the battery temperature sensor is correctly connected.
• Contact the Service.
• Ensure that the battery temperature sensor is correctly connected.
• Contact the Service.
• Replace the micro SD card.