SMA SUNNY ISLAND 4.4M Operating Manual page 143

Hide thumbs Also See for SUNNY ISLAND 4.4M:
Table of Contents

Advertisement

SMA Solar Technology AG
Event number
Message, cause and corrective measures
1402
Grid incident
The voltage of the generator or the utility grid at the Sunny Island at line conductor Lxx is out-
side the configured thresholds (redundant measurement).
Corrective measures for generator:
Corrective measures for utility grid:
1403
Grid incident
The Sunny Island at line disconnector Lxx disconnects from the external energy source be-
cause the ratio of AC voltage and battery voltage is too high. Either the voltage at connec-
tion AC2 is too high or the battery voltage too low.
Corrective measures:
1404
Grid incident
The Sunny Island at line conductor Lxx disconnects from the utility grid due to phase conduc-
tor failure/overload at terminal AC2.
Corrective measures:
1405
Grid incident
A short circuit is present at connection AC2 of the Sunny Island at line conductor Lxx.
Corrective measures:
1407
Grid incident
Disconnection from the utility grid due to non-compliance with the voltage-frequency ratio at
line conductor Lxx
Corrective measures:
Operating manual
• Change the voltage thresholds for the generator. As an aid to this, observe and
evaluate the measured values Voltage of external grid connection Lxx during
ongoing operation.
• If possible, adjust the generator voltage.
• Contact the Service.
• Contact the Service.
• Reduce the total power of the loads, e.g. by staggering their use over time.
• Ensure that there is not a short circuit present at connection AC2.
• Contact the Service.
• Contact the Service.
14 Troubleshooting
SI44M-80H-13-BE-en-15
143