KEB Combivert R6-S Instruction Manual page 43

Power supply and regenerative unit
Hide thumbs Also See for Combivert R6-S:
Table of Contents

Advertisement

No.
Name
CP.08
DC current
Resolution
0.1 A
No.
Name
CP.09
DC voltage
Resolution
1 V
No.
Name
CP.10
Peak DC voltage
Value range
0...1000 V
No.
Name
CP.11
Power module temperature
Resolution
1 °C
No.
Name
CP.12
OL counter display
Resolution
1 %
Monitoring and analysis parameters
Meaning
Display of the calculated DC output current in amperes.
Meaning
Display of actual DC link voltage in volt. The value is measured at the
DC output terminals of the COMBIVERT R6-S.
Meaning
Parameter CP.10 enables to recognize voltage peaks within an oper-
ating cycle. For that the highest value of CP.09 is stored in CP.10. The
peak value memory can be cleared by pressing the UP and DOWN key
or via bus by writing any value you like to the address of CP.10. Switch-
ing off COMBIVERT R6-S also clears the memory.
Meaning
Display of the actual power module temperature. On exceeding the
maximum power module temperature (see "Technical data") the mod-
ulation is switched off and error E.OH is displayed. Message E.nOH is
displayed after the cooling period. The error can be reset now.
Meaning
The permanent load of the COMBIVERT R6-S can be evaluated with
this parameter, in order to avoid an E.OL error (in-time load reduction).
Error E.OL is released, if the overload counter reaches 100 %.
r/w
Enter
based on
ru.15
r/w
Enter
based on
ru.19
r/w
Enter
based on
ru.20
r/w
Enter
based on
ru.38
r/w
Enter
based on
ru.39
GB - 43