Connection of the COMBIVERT R6
4.3.3
Terminals commutation reactor / harmonic filter
15/19Z1B05-1000 (commutation
15/19Z1C05-1000 (harmonic filter)
L1.1 L1.2 L2.1
PE
Table 10:
X2B, X2C, X2D RJ45 socket for phase
synchronization and temperature sen-
sor
Table 11:
GB - 28
reactor)
L2.2 L3.1 L3.2
PE
X2D
X2C
X2B
1
8
1
8
1
8
Commutation reactor / harmonic filter
1
8
RJ45-socket
permissible cable cross-section Size
Name
Function
L1.1
3-phase mains con-
L2.1
nection
L3.1
L1.2
L2.2
Output to COMBIV-
L3.2
ERT R6-S
X2B,-C,-D see below
Connection for shield-
PE
ing/earthing
No. Name
1
t1
2
t2
3
U13_syn
4
5
U21_syn
6
7
U32_syn
8
Tightening torque [Nm]
Size 15
2.5...16 mm²
(AWG 20...6)
Size 19
2.5...35 mm²
(AWG 12...2)
Function
Connection for temperature sen-
sor (optional)
Synchronization phase 1 / 3
reserved
Synchronization phase 2 / 1
reserved
Synchronization phase 3 / 2
reserved
15
1.2...2
Size
19
2.5...5
6