Operator - KEB Combivert R6-S Instruction Manual

Power supply and regenerative unit
Hide thumbs Also See for Combivert R6-S:
Table of Contents

Advertisement

Operator

4.6
Operator
An operator is required as an accessory for local or external operation of the COMBIVERT
R6-S. To avoid malfunctions, the COMBIVERT must be set to nOP status (open control re-
lease) before plugging/unplugging the operator. When the COMBIVERT is put into operation,
it is started with the last saved values or the factory setting.
Digital operator (part number 00F5060-1000)
Interface operator (part number 00F5060-2000)
x x 5-digit LED display
x x Operation/error display
Normal "LED on"
Error "LED flashes"
- x Interface control
BUS operation "LED on"
x x Double function keyboard
- x X6B HSP5 programming and diagnostic interface
- x X6C RS232/RS485
For serial data transmission to RS232 / 485 use only the operator interface. The
direct connection of a PC to the COMBIVERT is only permitted via a special
HSP5 cable (part number 00F50C0-0001) and would otherwise lead to the de-
struction of the PC interface!
X6C
5 4 3 2 1
5
4
9
8
9 8 7 6
GB - 38
PIN RS485 Signal Meaning
1
2
3
4
3
2
1
5
6
7
6
7
8
9
9 pole SUB-D socket
RS 232 cable
Part number
0058025-001D
Length 3 m
-
-
reserved
-
TxD
Transmission signal RS232
-
RxD
Receive signal RS232
A'
RxD-A Receive signal A RS485
B'
RxD-B Receive signal B RS485
-
VP
Supply voltage +5 V (Imax=50 mA)
C/C'
DGND Data reference potential
A
TxD-A Transmission signal A RS485
B
TxD-B Transmission signal B RS485
2
to the PC
3
5
START
ENTER
F/R
STOP
X6B
C O M B I V E R T
X6C
9 pole SUB-D socket
2
to the operator
3
7
Housing (PE)
FUNC.
SPEED
X6D