Monitoring And Analysis Parameters - KEB Combivert R6-S Instruction Manual

Power supply and regenerative unit
Hide thumbs Also See for Combivert R6-S:
Table of Contents

Advertisement

View of the work meter
The displayed values of the work meters only provide an estimated value due
to measurement and calculation inaccuracies. These displayed values are not
suitable for accounting purposes and cannot replace any measuring devices.
5.4

Monitoring and analysis parameters

The following parameters serve for the functional monitoring during operation.
No.
Name
CP.01
Inverter state
The status display shows the actual working condition of the COMBIVERT.
Status messages
rEGEn
Regeneration active (regenerative operation)
bbL
Count down of the base-block time, R6-S released
noP
"no Operation" control release not bridged, modulation switched off
Net off; regenerative operation is further possible, if the disconnecting time E.nEt
nEtoF
(Pn.14) > 0 s
Stb
R6-S regenerative unit in stand-by operation (motor operation)
Error Messages
"ERROR! drive overheat", temperature monitoring of the commutation reactor has
E.dOH
triggered and the waiting time has expired.
E.EF
"ERROR! external fault", error message by an external unit
"ERROR! Line frequency", the line frequency deviates more than 5 %. The max.
E.FnEt
mains frequency deviation can be adjusted in the application mode with CS.03.
ERROR! Charging circuit, load-shunt defective or wrong or input voltage too low.
E.LSF
This message is displayed for a short time during the power-on phase (no error
message follows).
E.nEt
"ERROR! net", one or more phases are missing
no E. overheat pow.mod. overheat pow.mod. temperature not present (E.OH),
E.nOH
error can be reset.
E.nOL
No Over Load, cooling time after E.OL is up , error can be reset.
E.OC
"ERROR! Overcurrent", output current too high or ground fault
"ERROR! Overheat pow.mod.", overheating at power module (see „Technical
E.OH
data")
E.OHI
"ERROR! Overheat internal", temperature in the interior > 70°C
E.OL
"ERROR! Overload", overload monitoring of the regenerative unit has responded
E.OP
"ERROR! Overpotential", DC link voltage too high
"ERROR! power flicker det.", mains interruption (phase) during the initialisation
E.Pfd
phase
E.Pu
"ERROR! power unit", power unit code is missing, load shunt relay defective
Monitoring and analysis parameters
r/w
Enter based on
ru.00
continued on the next page
GB - 41