4.5

Connection of the control board version S

4.5.1

Assignment of the control terminal strip X2A

Conductor cross-section 0.14...1.5 mm², tightening torque 0.22...0.25 Nm
PIN Function
10
24V input
11
Mass
12
Digital input 1
13
Digital input 2
14
Digital input 3
15
Digital input 4
16
Digital input or
output
17
24V output
18
Mass
19
Digital output 1
20
Digital output 2
21
Analog output
22
24V output
23
Mass
24
Relay 1 / NO con-
tact
25
Relay 1 / NC contact RLB
26
Relay 1 / switching
contact
27
Relay 2 / NO contact FLA
28
Relay 2 / NC contact FLB
29
Relay 2 / switching
contact
*) max. 1Aac is permissible for 125Vac.
Connection of the control board version S
10 11 12 13 14 15 16 17 18 19 20 21 22 23
Name
Default
Uin
COM
ST
I1
Set selection
I2
Set selection
I3
Ext. error
I/O (I4)
Uout
COM
O1
DC >600 V
O2
Error mes-
sage
ANOUT
Uout
COM
RLA
Ready for
operation (no
error)
RLC
DC > 600 V
FLC
X2A
24 25 26 27 28 29
Description
External supply of the control
board
Reference potential
Control release / reset
programmable
programmable
programmable
Active signal (connection of
all R6 in parallel operation in
master-slave mode)
Voltage supply for in and
outputs
Reference potential
Transistor output (DC >
CP.19)
Transistor output (error mes-
sage)
Difference to mains frequency
(CP.18)
see terminal 17
Reference potential
Relay output
Ready signal (Status "Stb" or
"rEGEn")
Relay output (DC > CP.19)
Specifications
21.6...26.4 V DC
/ 1 A
Ri: 4.4 kΩ
approx. 24 V /
max. 100 mA
Imax: 25 mA
Imax: 25 mA
0...±10 V / max.
5 mA
max. 30 V DC *)
0.01...2 A DC
max. 30 V DC *)
0.01...2 A DC