Heating actuator 6-gang with controller
Table of Contents

Advertisement

Heating actuator 6-gang with controller
The LEDs Open and Close indicate the valve status.
Temporary manual operation mode: After running through all of the outputs
the device exits manual operation mode after another brief actuation.
Operating all outputs simultaneously
The device is in permanent manual operation mode.
Press the ALL OP / CL button.
All the valves open and close alternately.
In contrast to the operating function using the OPEN or CLOSE buttons, the actuator
always activates the valve outputs with a constant signal (0% or 100%), when they
are activated simultaneously. This causes the valves to close or open completely. No
pulse width modulation is executed.
Disabling individual outputs
The device is in permanent manual operation mode.
Press the ǃ button briefly as many times as necessary until the desired out-
put is selected.
The status LED of the selected output flashes.
Press buttons Open and Close simultaneously for at least 5 seconds.
Selected output is disabled.
The status LED of the disabled output flashes quickly.
Deactivate permanent manual operation mode (see chapter "Operation"
Page 8).
A disabled output can be operated in manual operation mode.
Re-enabling outputs
The device is in permanent manual operation mode.
Press the ǃ button briefly as many times as necessary until the desired out-
put is selected.
Press buttons Open and Close simultaneously for at least 5 seconds.
Selected output is enabled.
Status LED of the enabled output flashes slowly.
Deactivate permanent manual operation mode (see chapter "Operation"
Page 8).