Settings; Information List - Siemens SIPROTEC 7SC80 Series Manual

Feeder automation controller
Hide thumbs Also See for SIPROTEC 7SC80 Series:
Table of Contents

Advertisement

Functions
2.6 Negative Sequence Protection 46
2.6.4

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
4001
FCT 46
4002
46-1 PICKUP
4003
46-1 DELAY
4004
46-2 PICKUP
4005
46-2 DELAY
4006
46 IEC CURVE
4007
46 ANSI CURVE
4008
46-TOC PICKUP
4009
46-TOC TIMEDIAL
4010
46-TOC TIMEDIAL
4011
46-TOC RESET
4012A
46 T DROP-OUT
2.6.5

Information List

No.
Information
5143
>BLOCK 46
5151
46 OFF
5152
46 BLOCKED
5153
46 ACTIVE
5159
46-2 picked up
5165
46-1 picked up
5166
46-TOC pickedup
5170
46 TRIP
5171
46 Dsk pickedup
114
C
Setting Options
OFF
ON
1A
0.10 .. 3.00 A
5A
0.50 .. 15.00 A
0.00 .. 60.00 sec; ∞
1A
0.10 .. 3.00 A
5A
0.50 .. 15.00 A
0.00 .. 60.00 sec; ∞
Normal Inverse
Very Inverse
Extremely Inv.
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
1A
0.10 .. 2.00 A
5A
0.50 .. 10.00 A
0.50 .. 15.00 ; ∞
0.05 .. 3.20 sec; ∞
Instantaneous
Disk Emulation
0.00 .. 60.00 sec
Type of In-
formation
SP
>BLOCK 46
OUT
46 switched OFF
OUT
46 is BLOCKED
OUT
46 is ACTIVE
OUT
46-2 picked up
OUT
46-1 picked up
OUT
46-TOC picked up
OUT
46 TRIP
OUT
46 Disk emulation picked up
Default Setting
OFF
46 Negative Sequence
Protection
0.10 A
46-1 Pickup
0.50 A
1.50 sec
46-1 Time Delay
0.50 A
46-2 Pickup
2.50 A
1.50 sec
46-2 Time Delay
Extremely Inv.
IEC Curve
Extremely Inv.
ANSI Curve
0.90 A
46-TOC Pickup
4.50 A
5.00
46-TOC Time Dial
0.50 sec
46-TOC Time Dial
Instantaneous
46-TOC Drop Out
0.00 sec
46 Drop-Out Time Delay
Comments
SIPROTEC, 7SC80, Manual
E50417-G1140-C486-A1, Release date 12.2011