Information List - Siemens SIPROTEC 7SC80 Series Manual

Feeder automation controller
Hide thumbs Also See for SIPROTEC 7SC80 Series:
Table of Contents

Advertisement

Addr.
Parameter
5103
27-1 PICKUP
5106
27-1 DELAY
5110
27-2 PICKUP
5111
27-2 PICKUP
5112
27-2 DELAY
5113A
27-1 DOUT RATIO
5114A
27-2 DOUT RATIO
5120A
CURRENT SUPERV.
5130
27-1 PhA Pickup
5131
27-1 PhA Pickup
5132
27-1 PhB Pickup
5133
27-1 PhB Pickup
5134
27-1 PhC Pickup
5135
27-1 PhC Pickup
5136
27-2 PhA Pickup
5137
27-2 PhA Pickup
5138
27-2 PhB Pickup
5139
27-2 PhB Pickup
5140
27-2 PhC Pickup
5141
27-2 PhC Pickup
5142
27-1 PhA Delay
5143
27-1 PhB Delay
5144
27-1 PhC Delay
5145
27-2 PhA Delay
5146
27-2 PhB Delay
5147
27-2 PhC Delay
2.4.6

Information List

No.
Information
234.2100 27, 59 blk
2203
27-1 PhA pickup
2204
27-1 PhB pickup
2205
27-1 PhC pickup
2206
27-1 PhA PU CS
2207
27-1 PhB PU CS
2208
27-1 PhC PU CS
2209
27-2 PhA pickup
SIPROTEC, 7SC80, Manual
E50417-G1140-C486-A1, Release date 12.2011
Setting Options
10 .. 200 V
0.00 .. 100.00 sec; ∞
10 .. 385 V
10 .. 200 V
0.00 .. 100.00 sec; ∞
1.01 .. 3.00
1.01 .. 3.00
OFF
ON
10 .. 385 V
10 .. 200 V
10 .. 385 V
10 .. 200 V
10 .. 385 V
10 .. 200 V
10 .. 385 V
10 .. 200 V
10 .. 385 V
10 .. 200 V
10 .. 385 V
10 .. 200 V
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
Type of In-
formation
IntSP
27, 59 blocked via operation
OUT
27-1 Phase A Undervoltage pickup
OUT
27-1 Phase B Undervoltage pickup
OUT
27-1 Phase C Undervoltage pickup
OUT
27-1 Phase A PICKUP w/curr. Supervision
OUT
27-1 Phase B PICKUP w/curr. Supervision
OUT
27-1 Phase C PICKUP w/curr. Supervision
OUT
27-2 Phase A Undervoltage pickup
Default Setting
45 V
27-1 Pickup
1.50 sec
27-1 Time Delay
70 V
27-2 Pickup
40 V
27-2 Pickup
0.50 sec
27-2 Time Delay
1.20
27-1 Dropout Ratio
1.20
27-2 Dropout Ratio
ON
Current Supervision
75 V
27-1 Phase A Pickup
45 V
27-1 Phase A Pickup
75 V
27-1 Phase B Pickup
45 V
27-1 Phase B Pickup
75 V
27-1 Phase C Pickup
45 V
27-1 Phase C Pickup
70 V
27-2 Phase A Pickup
40 V
27-2 Phase A Pickup
70 V
27-2 Phase B Pickup
40 V
27-2 Phase B Pickup
70 V
27-2 Phase C Pickup
40 V
27-2 Phase C Pickup
1.50 sec
27-1 Phase A Time Delay
1.50 sec
27-1 Phase B Time Delay
1.50 sec
27-1 Phase C Time Delay
0.50 sec
27-2 Phase A Time Delay
0.50 sec
27-2 Phase B Time Delay
0.50 sec
27-2 Phase C Time Delay
Comments
Functions
2.4 Voltage Protection 27, 59
Comments
101