Setting Notes - Siemens SIPROTEC 7SC80 Series Manual

Feeder automation controller
Hide thumbs Also See for SIPROTEC 7SC80 Series:
Table of Contents

Advertisement

2.12.2

Setting Notes

The setting of the functional scope determines the number of flexible protection functions to be used (see
Chapter 2.1.1). If a flexible function in the functional scope is disabled (by removing the checkmark), this will
result in losing all settings and configurations of this function or its settings will be reset to their default settings.
General
In the DIGSI setting dialog „General", parameter FLEXIBLE FUNC. can be set to OFF, ON or Alarm Only. If
the function is enabled in operational mode Alarm Only, no faults are recorded, no „Effective"-indication is
generated, no trip command issued and neither will the circuit-breaker protection be affected. Therefore, this
operational mode is preferred when a flexible function is not required to operate as a protection function. Fur-
thermore, the OPERRAT. MODE can be configured:
Three-phase – functions evaluate the three-phase measuring system, i.e. all three phases are processed si-
multaneously. A typical example is the three-phase operating time overcurrent protection.
Single-phase – functions evaluate only the individual measuring value. This can be an individual phase value
(e.g. V
) or a ground variable (V
B
Setting no reference determines the evaluation of measured variables irrespective of a single or three-
phase connection of current and voltage. Table 2-10 provides an overview regarding which variables can be
used in which mode of operation.
Measured Variable:
In the setting dialog „Measured Variable" the measured variables to be evaluated by the flexible protection func-
tions can be selected, which may be a calculated or a directly measured variable. The setting options that can
be selected here are dependent on the mode of measured-value processing as predefined in parameter
OPERRAT. MODE (see the following table).
Table 2-11
Parameters "Operating Mode" and "Measured Quantity"
Parameter OPERRAT. MODE
Setting
Single-phase
Three-phase
Without reference
If at address 213 VT Connect. 3ph you selected Vab, Vbc as type of connection of the voltage transform-
ers, the power values are not available.
Measurement Procedures
The measurement procedures as set out in the following table can be configured for the measured variables -
current, voltage and power. The dependencies of the available measurement procedures of configurable
modes of operation and the measured variable are also indicated.
SIPROTEC, 7SC80, Manual
E50417-G1140-C486-A1, Release date 12.2011
or I
).
N
N
Parameter MEAS. QUANTITY
Setting options
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
Frequency
df/dt rising
df/dt falling
Binray Input
Functions
2.12 Flexible Protection Functions
149