Siemens SIPROTEC 7SC80 Series Manual page 297

Feeder automation controller
Hide thumbs Also See for SIPROTEC 7SC80 Series:
Table of Contents

Advertisement

Addr.
Parameter
614A
OP. QUANTITY 59
615A
OP. QUANTITY 27
620
Remote FwUpdate
640
Start image DD
1101
FullScaleVolt.
1102
FullScaleCurr.
1103
RE/RL
1104
XE/XL
1105
x'
1106
x'
1108
P,Q sign
1109
Line angle
1110
Line length
1111
Line length
1201
FCT 50/51
1202
50-2 PICKUP
1203
50-2 DELAY
1204
50-1 PICKUP
1205
50-1 DELAY
1213A
MANUAL CLOSE
1214A
50-2 active
1215A
50 T DROP-OUT
1216A
50-3 active
1217
50-3 PICKUP
1218
50-3 DELAY
1219A
50-3 measurem.
1220A
50-2 measurem.
1221A
50-1 measurem.
1301
FCT 50N/51N
SIPROTEC, 7SC80, Manual
E50417-G1140-C486-A1, Release date 12.2011
Function
C
Setting Options
P.System Data 1
Vphph
Vphph selective
Vph-n
Vph-n selective
V1
V2
P.System Data 1
V1
Vphph
Vphph selective
Vph-n
Vph-n selective
Device, General
Disabled
Enabled
Device, General
image 1
image 2
image 3
image 4
image 5
image 6
P.System Data 2
0.10 .. 800.00 kV
P.System Data 2
10 .. 50000 A
P.System Data 2
-0.33 .. 7.00
P.System Data 2
-0.33 .. 7.00
0.0050 .. 15.0000 Ω/mi
P.System Data 2
1A
0.0010 .. 3.0000 Ω/mi
5A
0.0050 .. 9.5000 Ω/km
P.System Data 2
1A
0.0010 .. 1.9000 Ω/km
5A
P.System Data 2
not reversed
reversed
P.System Data 2
10 .. 89 °
P.System Data 2
0.1 .. 1000.0 km
P.System Data 2
0.1 .. 650.0 Miles
50/51 Overcur.
ON
OFF
0.10 .. 35.00 A; ∞
50/51 Overcur.
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
0.10 .. 35.00 A; ∞
50/51 Overcur.
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
50/51 Overcur.
50-3 instant.
50-2 instant.
50 -1 instant.
Inactive
50/51 Overcur.
Always
50/51 Overcur.
0.00 .. 60.00 sec
50/51 Overcur.
Always
1.00 .. 35.00 A; ∞
50/51 Overcur.
1A
5.00 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
50/51 Overcur.
Fundamental
True RMS
Instantaneous
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
ON
OFF
Default Setting
Vphph
Opera. Quantity for 59 Overvolt.
Prot.
V1
Opera. Quantity for 27 Undervolt.
Prot.
Enabled
Remote firmware update
image 1
Start image Default Display
20.00 kV
Measurem:FullScaleVolt-
age(Equipm.rating)
400 A
Measurem:FullScaleCur-
rent(Equipm.rating)
1.00
Zero seq. compensating factor
RE/RL
1.00
Zero seq. compensating factor
XE/XL
0.2420 Ω/mi
feeder reactance per mile: x'
0.0484 Ω/mi
0.1500 Ω/km
feeder reactance per km: x'
0.0300 Ω/km
not reversed
P,Q operational measured values
sign
85 °
Line angle
100.0 km
Line length in kilometer
62.1 Miles
Line length in miles
ON
50, 51 Phase Time Overcurrent
4.00 A
50-2 Pickup
20.00 A
0.00 sec
50-2 Time Delay
1.00 A
50-1 Pickup
5.00 A
0.50 sec
50-1 Time Delay
50-2 instant.
Manual Close Mode
Always
50-2 active
0.00 sec
50 Drop-Out Time Delay
Always
50-3 active
∞ A
50-3 Pickup
∞ A
0.00 sec
50-3 Time Delay
Fundamental
50-3 measurement of
Fundamental
50-2 measurement of
Fundamental
50-1 measurement of
ON
50N, 51N Ground Time Overcur-
rent
Appendix
A.8 Settings
Comments
297