Overvoltage Protection 59

Function
The overvoltage protection has two elements. In case of a high overvoltage, tripping switch off is performed
with a short-time delay, whereas in case of less severe overvoltages, the tripping is performed with a longer
time delay. When one of the adjustable settings is exceeded, the 59 element picks up and trips after an adjust-
able time delay has elapsed. The time delay is not dependent on the magnitude of the overvoltage.
The dropout ratio for the two overvoltage elements (= V
The pickup voltages and time delays can also be set phase-specifically.
The following figure shows the logic diagram of the overvoltage protection function.
The logic diagram also applies for overvoltage protection which can be set phase-specifically (Vphph
selective or Vph-n selective). The thresholds and time delays are to be replaced with the phase-spe-
cific values.
SIPROTEC, 7SC80, Manual
E50417-G1140-C486-A1, Release date 12.2011
2.4 Voltage Protection 27, 59
/V
) can be set.
dropout value
pickup value
Functions
91