Oscillographic Fault Records

The Multifunctional Protection with Control 7SC80 is equipped with a fault record memory. The instantaneous
values of the measured values
i
, i
, i
, i
and v
A
B
C
N
(voltages depending on connection) are sampled at intervals of 1.0 ms (at 50 Hz) and stored in a revolving
buffer (20 samples per cycle). In the event of a fault, the data is stored for a set period of time, but not for more
than 6 seconds. Up to 8 fault events can be recorded in this buffer. The fault record memory is automatically
updated with every new fault so that there is no acknowledgment for previously recorded faults required. In ad-
dition to protection pickup, the recording of the fault event data can also be started via a binary input or via the
serial interface.

2.1.4.1 Description

The data of a fault event can be read out via the device interface and evaluated with the help of the SIGRA 4
graphic analysis software. SIGRA 4 graphically represents the data recorded during the fault event and also
calculates additional information from the measured values. Currents and voltages can be presented either as
primary or as secondary values. Signals are additionally recorded as binary tracks (marks), e.g. "pickup", "trip".
If port F of the device has been configured correspondingly, the fault record data can be imported by a central
controller via this interface and evaluated. Currents and voltages are prepared for a graphic representation.
Signals are additionally recorded as binary tracks (marks), e.g. "pickup", "trip".
The retrieval of the fault data by the central controller takes place automatically either after each protection
pickup or after a tipping.
Depending on the selected type of connection of the voltage transformers (address 213 VT Connect. 3ph),
the following measured values are recorded in the fault record:
Voltage connection
Van, Vbn, Vcn
V
AB
V
BC
V
CA
V
A
V
B
V
C
The voltage connection Vx is always available.
Note
The signals used for the binary tracks can be allocated in DIGSI.
42
, v
, v
, v
, v
, v
, v
, v
A
B
C
AB
BC
CA
N
Vab, Vbc, VGnd
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
X
Vab, Vbc
Yes
Yes
Yes
E50417-G1140-C486-A1, Release date 12.2011
SIPROTEC, 7SC80, Manual

Advertisement

Table of Contents
loading

Table of Contents