Definite-Time Overcurrent Protection 50, 50N - Siemens SIPROTEC 7SC80 Series Manual

Feeder automation controller
Hide thumbs Also See for SIPROTEC 7SC80 Series:
Table of Contents

Advertisement

Technical Data

4.2 Definite-time overcurrent protection 50, 50N

4.2
Definite-time overcurrent protection 50, 50N
Operating Modes
Three-phase
Two-phase
Method of Measurement
All elements
50-3, 50N-3
Setting Ranges/Increments
Current pickup 50-1, 50-2 (phases)
Current pickup 50-3 (phases)
Current pickup 50N-1, 50N-2
(ground)
Current pickup 50N-3 (ground)
Delay times T
Dropout delay times 50 T DROP-OUT,
50N T DROP-OUT
Times
Pickup times (without inrush restraint, with inrush restraint + 1 cycle)
Fundamental component, RMS value
- for setting value x 2
- for setting value x 10
Instantaneous value
- for setting value x 2
- for setting value x 10
Dropout times
Fundamental component, RMS value
Instantaneous value
242
Standard
Phases A and C
Fundamental wave, true RMS value
Additional instantaneous values
0.10 A to 35.00 A or ∞ (disabled)
for I
=
Nom
1 A
0.50 A to 175.00 A or ∞ (disabled)
for I
=
Nom
5 A
1.0 A to 35.00 A or ∞ (disabled)
for I
=
Nom
1 A
5.0 A to 175.00 A or ∞ (disabled)
for I
=
Nom
5 A
0.05 A to 35.00 A or ∞ (disabled)
for I
=
Nom
1 A
0.25 A to 175.00 A or ∞ (disabled)
for I
=
Nom
5 A
0.25 A to 35.00 A or ∞ (disabled)
for I
=
Nom
1 A
1.25 A to 175.00 A or ∞ (disabled)
for I
=
Nom
5 A
0.00 s to 60.00 s or ∞ (disabled)
0.00 s to 60.00 s
approx. 30 ms
approx. 20 ms
approx. 16 ms
approx. 16 ms
approx. 30 ms
approx. 40 ms
Increments
0.01 A
Increments
0.01 A
Increments
0.01 s
Increments
0.01 s
SIPROTEC, 7SC80, Manual
E50417-G1140-C486-A1, Release date 12.2011