Functions
2.4 Voltage Protection 27, 59
2.4.5

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr.
Parameter
5001
FCT 59
5002
59-1 PICKUP
5003
59-1 PICKUP
5004
59-1 DELAY
5005
59-2 PICKUP
5006
59-2 PICKUP
5007
59-2 DELAY
5015
59-1 PICKUP V2
5016
59-2 PICKUP V2
5017A
59-1 DOUT RATIO
5018A
59-2 DOUT RATIO
5019
59-1 PICKUP V1
5020
59-2 PICKUP V1
5030
59-1 PhA Pickup
5031
59-1 PhA Pickup
5032
59-1 PhB Pickup
5033
59-1 PhB Pickup
5034
59-1 PhC Pickup
5035
59-1 PhC Pickup
5036
59-2 PhA Pickup
5037
59-2 PhA Pickup
5038
59-2 PhB Pickup
5039
59-2 PhB Pickup
5040
59-2 PhC Pickup
5041
59-2 PhC Pickup
5042
59-1 PhA Delay
5043
59-1 PhB Delay
5044
59-1 PhC Delay
5045
59-2 PhA Delay
5046
59-2 PhB Delay
5047
59-2 PhC Delay
5101
FCT 27
5102
27-1 PICKUP
100
Setting Options
OFF
ON
Alarm Only
20 .. 415 V
20 .. 240 V
0.00 .. 100.00 sec; ∞
20 .. 260 V
20 .. 240 V
0.00 .. 100.00 sec; ∞
2 .. 240 V
2 .. 240 V
0.90 .. 0.99
0.90 .. 0.99
20 .. 240 V
20 .. 240 V
20 .. 415 V
20 .. 240 V
20 .. 415 V
20 .. 240 V
20 .. 415 V
20 .. 240 V
20 .. 415 V
20 .. 240 V
20 .. 415 V
20 .. 240 V
20 .. 415 V
20 .. 240 V
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
OFF
ON
Alarm Only
10 .. 385 V
Default Setting
OFF
59 Overvoltage Protection
110 V
59-1 Pickup
110 V
59-1 Pickup
0.50 sec
59-1 Time Delay
120 V
59-2 Pickup
120 V
59-2 Pickup
0.50 sec
59-2 Time Delay
30 V
59-1 Pickup V2
50 V
59-2 Pickup V2
0.95
59-1 Dropout Ratio
0.95
59-2 Dropout Ratio
110 V
59-1 Pickup V1
120 V
59-2 Pickup V1
110 V
59-1 Phase A Pickup
110 V
59-1 Phase A Pickup
110 V
59-1 Phase B Pickup
110 V
59-1 Phase B Pickup
110 V
59-1 Phase C Pickup
110 V
59-1 Phase C Pickup
120 V
59-2 Phase A Pickup
120 V
59-2 Phase A Pickup
120 V
59-2 Phase B Pickup
120 V
59-2 Phase B Pickup
120 V
59-2 Phase C Pickup
120 V
59-2 Phase C Pickup
0.50 sec
59-1 Phase A Time Delay
0.50 sec
59-1 Phase B Time Delay
0.50 sec
59-1 Phase C Time Delay
0.50 sec
59-2 Phase A Time Delay
0.50 sec
59-2 Phase B Time Delay
0.50 sec
59-2 Phase C Time Delay
OFF
27 Undervoltage Protection
75 V
27-1 Pickup
E50417-G1140-C486-A1, Release date 12.2011
Comments
SIPROTEC, 7SC80, Manual