6 | Installation and electrical connection
6.3
Using a 1-phase AC mains
connection
Fig. 8
1.
Insert the AC mains cable into the charging station from
the left cable gland at the bottom of the station.
Fig. 9
Terminal
Function
1
Earth
2
AC Neutral
3
AC L1
1.
Insert the wires into the terminal block following the colour
coding in the legend.
2.
Tighten the screws on the terminal block with a torque of
2.5 Nm.
10 / 37
Fig. 10
3.
4.
5.
3
2
1
Wire colour
Green-Yellow
Blue
Brown
Fig. 11
6.
7.
If you mount the charging station on a conductive metal
surface, such as a metal pole, you must make a connection
to the earth using an extension wire for the earth (ground)
and the screw at the lower right.
Change the position of the grounding wire from A to B to
ensure grounding.
– Insert the plastic support (this is the IP rubber supplied in
the unit's accessory pack) into the fixing hole (position
"B").
– Secure the grounding cable using an M6 x 30 screw,
which is in the artwork pack. This screw also secures the
unit to a conductive metal surface (where applicable).
Tighten the cable glands before closing the charging sta-
tion cover (See chapter 6.5, "Using the cable glands" on
page 12).
L1
L2
L3
L3
L2
Wiring diagram (for IT Grid Installation only)
WARNING
for IT Grid Installation only
A maximum rated voltage of 230 V is permissible
between L1 and L3 on the grid side.
For single-phase IT Grid installation, use the above wiring
diagram.
In the web user interface, set the grounding type to "IT
Grid" using the "Installation settings" menu
B
A
L1
L2
L3
L1
N
G
230 V
5111967A OI-II Webasto Unite