Modbus Address Map - HMS Intesis INMBSPAN016O000 User Manual

Modbus server panasonic vrf air conditioning gateway for the integration of panasonic vrf systems into modbus (rtu and tcp) systems
Table of Contents

Advertisement

Modbus Server – Panasonic
TM
Intesis

2.4. Modbus Address Map

Modbus address from the formula is expressed in link layer format. This is, first register address is 0.
Read
Modbus Address
/Write
First Address is 0
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
1
([OU]
* 25) +
(([L] - 1) * 10000) +
7000) + 0
1
Where [OU] is the outdoor unit number. Values from 1 to 30.
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
Register/signal name
OCCUPANCY SIGNALS
R/W
Occupancy Cool Setpoint (x10)
R/W
Occupancy Heat Setpoint (x10)
R/W
Unoccupancy Cool Setpoint (x10)
R/W
Unoccupancy Heat Setpoint (x10)
R/W
Occupancy Continuous Check
R/W
Unoccupancy Deadband Action
GENERAL SIGNALS (all units)
W
On (all the units)
W
Off (all the units)
W
Operation Mode Auto (all the units)
W
Operation Mode Heat (all the units)
W
Operation Mode Dry (all the units)
W
Operation Mode Fan (all the units)
W
Operation Mode Cool (all the units)
W
Fan Speed Auto (all the units)
W
Fan Speed Low (all the units)
W
Fan Speed Mid (all the units)
W
Fan Speed High (all the units)
W
Vanes Position Stop (all the units)
W
Vanes Position 1 (all the units)
W
Vanes Position 2 (all the units)
W
Vanes Position 3 (all the units)
W
Vanes Position 4 (all the units)
W
Vanes Position 5 (all the units)
W
Vanes Swing (all the units)
W
Temperature Setpoint (all units) (x10ºC/ºF)
OUTDOOR UNITS SIGNALS
R
Communication Error OU
User Manual r1.1 EN
Possible values
-15...60ºC
4...140ºF
-15...60ºC
4...140ºF
-15...60ºC
4...140ºF
-15...60ºC
4...140ºF
0-Disabled, 1-Enabled
0-Off, 1-Current mode
1-Set all the units On
1-Set all the units Off
1-Set Auto Mode
1-Set Heat Mode
1-Set Dry Mode
1-Set Fan Mode
1-Set Cool Mode
1-Set Fan Speed Auto
1-Set Fan Speed Low
1-Set Fan Speed Med
1-Set Fan Speed High
1-Set Vanes Position Stop
1-Set Vanes Position 1
1-Set Vanes Position 2
1-Set Vanes Position 3
1-Set Vanes Position 4
1-Set Vanes Position 5
1-Set Vanes to Swing
16..30°C
0-No error, 1-Error
URL
https://www.intesis.com
9 / 36