Modbus Server – Panasonic
TM
Intesis
Error
Error in
Code
Control Panel
106
F10
107
F11
108
F12
109
F13
112
F16
113
F17
114
F18
116
F20
119
F23
120
F24
125
F29
126
F30
127
F31
129
H01
130
H02
131
H03
133
H05
134
H06
135
H07
136
H08
139
H11
140
H12
141
H13
143
H15
149
H21
150
H22
151
H23
153
H25
155
H27
156
H28
159
H31
193
L01
194
L02
195
L03
196
L04
197
L05
198
L06
199
L07
200
L08
201
L09
202
L10
203
L11
205
L13
207
L15
208
L16
209
L17
210
L18
211
L19
213
L21
225
P01
226
P02
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
Error category
Error Description
Indoor inlet temp sensor failure
Indoor outlet temp sensor failure
Outdoor Intake sensor failure (TS)
GHP - Cooling water temperature sensor failure
Outdoor High pressure sensor failure
GHP - Cooling water temperature sensor fault
GHP - Exhaust gas temperature sensor fault
GHP Clutch coil temperature fault
Outdoor Heat Exch temp sensor failure (EXG2)
Outdoor Heat Exch temp sensor failure (EXL2)
Indoor EEPROM error
Clock Function (RTC) fault
Outdoor EEPROM error
Compressor Fault, Over current (Comp1)
Compressor Fault, Locked rota current detected (Comp1)
Compressor Fault, No current detected (Comp1)
Compressor Fault, Discharge temp not detected (Comp1)
Compressor Fault, Low Pressure trip
Compressor Fault, Low oil level
Compressor Fault, Oil sensor Fault (Comp1)
Compressor Fault, Over current (Comp2)
Compressor Fault, Locked rota current detected (Comp2)
Compressor
Issues
Compressor Fault, No current detected (Comp2)
Compressor Fault, Discharge temp not detected (Comp2)
Compressor Fault, Over current (Comp3)
Compressor Fault, Locked rota current detected (Comp3)
Compressor Fault, No current detected (Comp3)
Compressor Fault, Discharge temp not detected (Comp3)
Compressor Fault, Oil sensor fault (Comp2)
Compressor Fault. Oil sensor (connection failure)
Compressor Fault. IPM trip (IMP current on temperature)
Setting Error, Indoor unit group setting error
Setting Error, Indoor/outdoor unit type/model miss-matched
Duplication of main indoor unit address in group control
Duplication of outdoor unit system address
2 or more controllers have been set as 'priority' in one system -
shown on controllers set as 'priority'
2 or more controllers have been set as 'priority' in one system -
shown on controllers not set as 'priority'
Group wiring connected on and individual indoor unit
Indoor unit address/group not set
Incorrect Settings
Indoor unit capacity code not set
Outdoor unit capacity code not set
Group control wiring incorrect
Indoor unit type setting error, capacity
Indoor unit paring fault
Water heat exch unit setting failure
Miss-match of outdoor unit with different refrigerant
4-way valve failure
Water heat exch unit duplicated address
Gas type setup failure
Indoor unit fault, Fan motor thermal overload
Indoor Unit
Outdoor unit fault, Compressor motor thermal overload, over or
Problems
under voltage