Modbus Server – Panasonic
TM
Intesis
Read
Modbus Address
/Write
First Address is 0
([IU] * 100) +
(([L]- 1) * 10000) + 20
([IU] * 100) +
W(T)
(([L]- 1) * 10000) + 21
([IU] * 100) +
(([L]- 1) * 10000) + 22
([IU] * 100) +
(([L]- 1) * 10000) + 23
([IU] * 100) +
(([L]- 1) * 10000) + 24
([IU] * 100) +
(([L]- 1) * 10000) + 25
([IU] * 100) +
(([L]- 1) * 10000) + 26
([IU] * 100) +
(([L]- 1) * 10000) + 27
([IU] * 100) +
(([L]- 1) * 10000) + 28
([IU] * 100) +
(([L]- 1) * 10000) + 29
([IU] * 100) +
(([L]- 1) * 10000) + 30
([IU] * 100) +
(([L]- 1) * 10000) + 31
([IU] * 100) +
(([L]- 1) * 10000) + 32
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
Register/signal name
R
Filter Alarm
Filter Alarm reset
R
Communication Error IU
R/W
Allow On/Off from remote controller
R/W
Allow Mode from remote controller
R/W
Allow Setpoint from remote controller
R
Unit type
R/W
Occupancy
RW
Modbus ambient temperature (x10)
R
AC Real Temperature Setpoint (x10)
R
Consumption Yesterday (kWh)
R
Consumption Today (kWh)
R
Consumption Total (kWh)
User Manual r1.1 EN
Possible values
0-Normal, 1-Alarm
1-Reset
0-No error, 1-Error
0-Allow, 1-Not allow
0-Allow, 1-Not allow
0-Allow, 1-Not allow
0-Not defined, 1-TBD, 2-GHP, 3-PAC,
4-VRF
1-Occupied, 2-Unoccupied, 3-Disable
ºC/ºF
ºC/ºF
kWh
kWh
kWh