HMS Intesis INMBSPAN016O000 User Manual page 11

Modbus server panasonic vrf air conditioning gateway for the integration of panasonic vrf systems into modbus (rtu and tcp) systems
Table of Contents

Advertisement

Modbus Server – Panasonic
TM
Intesis
Read
Modbus Address
/Write
First Address is 0
([IU] * 100) +
(([L]- 1) * 10000) + 20
([IU] * 100) +
W(T)
(([L]- 1) * 10000) + 21
([IU] * 100) +
(([L]- 1) * 10000) + 22
([IU] * 100) +
(([L]- 1) * 10000) + 23
([IU] * 100) +
(([L]- 1) * 10000) + 24
([IU] * 100) +
(([L]- 1) * 10000) + 25
([IU] * 100) +
(([L]- 1) * 10000) + 26
([IU] * 100) +
(([L]- 1) * 10000) + 27
([IU] * 100) +
(([L]- 1) * 10000) + 28
([IU] * 100) +
(([L]- 1) * 10000) + 29
([IU] * 100) +
(([L]- 1) * 10000) + 30
([IU] * 100) +
(([L]- 1) * 10000) + 31
([IU] * 100) +
(([L]- 1) * 10000) + 32
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
Register/signal name
R
Filter Alarm
Filter Alarm reset
R
Communication Error IU
R/W
Allow On/Off from remote controller
R/W
Allow Mode from remote controller
R/W
Allow Setpoint from remote controller
R
Unit type
R/W
Occupancy
RW
Modbus ambient temperature (x10)
R
AC Real Temperature Setpoint (x10)
R
Consumption Yesterday (kWh)
R
Consumption Today (kWh)
R
Consumption Total (kWh)
User Manual r1.1 EN
Possible values
0-Normal, 1-Alarm
1-Reset
0-No error, 1-Error
0-Allow, 1-Not allow
0-Allow, 1-Not allow
0-Allow, 1-Not allow
0-Not defined, 1-TBD, 2-GHP, 3-PAC,
4-VRF
1-Occupied, 2-Unoccupied, 3-Disable
ºC/ºF
ºC/ºF
kWh
kWh
kWh
URL
https://www.intesis.com
11 / 36