Install The Mounting Shelf - Juniper PTX3000 Quick Start Manual

Packet transport router
Hide thumbs Also See for PTX3000:
Table of Contents

Advertisement

PTX3000 Packet Transport Router Quick Start

Install the Mounting Shelf

6
Table 1: Mounting Hole Locations for Installing a PTX3000 Mounting Shelf
Hole
Distance Above U Division
1
0.02 in. (.06 cm)
2
0.2 in. (0.4 cm)
Insert cage nuts in the holes specified for mounting the chassis (see
2.
Table 2 on page
6).
Table 2: Mounting Hole Locations for Installing a Chassis
Hole
Distance Above U Division
1
4.9 in. (12.5 cm)
2
15.4 in. (39.1 cm)
3
29.9 in. (76.0 cm)
Optionally, you can install the mounting shelf before mounting the chassis in the rack.
To install the mounting shelf (see
Align the mounting shelf with the mounting holes on the rack rail.
1.
Partially insert a mounting screw appropriate for your rack into the holes specified in
2.
Table 1 on page
6.
Tighten all the screws completely to secure the mounting shelf to the rack rails.
3.
Figure 2: Installing the Mounting Hardware
Figure 2 on page
6):
Copyright © 2014, Juniper Networks, Inc.