8.3.3 Miscellaneous issues

Issue
Fumes and High Humidity
'Ghost' call for heat.
Error: Water High Limit / Low Water
Cutoff won't clear.
DHW taking too long to heat.
Boiler output not modulating up to
maximum despite target not being
reached.
Miscellaneous issues
Diagnosis
Improperly
Refer to installation/operation
installed
instructions.
condensate
trap
Leak in vent
Inspect using soap solution.
piping
Flue gas leak
Visually inspect all mechanical
within boiler
connections.
Triac or
Remove Therm. connections from
'Power-
boiler to confirm that stray voltage, or
robbing'
current induced in thermostat wiring, is
thermostat
source of nuisance signal. Replace the
sending
Power Robbing thermostat, isolate the
current to
thermostat with a relay or install a
boiler.
properly sized resistor (consult the
thermostat manufacturer first then IBC
for instructions).
Boiler is in 1-
For instructions on clearing errors, see
hour safety
the V10 Touchscreen Controller
lockout.
manual.
Sensor may be
Check sensor engagement; note well is
under-reading
15 cm / almost 6 inches deep and
actual water
sensor must be fully set to back. Check
temp.
programmed settings boiler temp set
too close to the required DHW
temperature.
Possible flow
Confirm that the boiler pump is able to
issue: check
overcome head loss of boiler and
for 35 or 40 °F
primary loop piping at the required flow
temperature
rate.
difference
between boiler
supply and
return water
temperatures
(evokes
electronic
fence).
98
Section: Troubleshooting
Fix