POWERVALUE 11 RT G2 IN — 1-3 KVA

4. Operation

This chapter describes how the UPS is operated
through the LCD.
The user can:
Operate the LCD
Start up and shut down the UPS (excluding the
commissioning start up)
Operate additional SNMP adapters and their
software

4 .1 Control panel

The user-friendly control panel has two parts:

Selection keys

Power management LCD (PMD)

LCD

Selection
4.1-1
Control panel
4.1.1 Selection keys
Table 2: UPS selection keys
Button
ON/MUTE
OFF/ENTER
SELECT
ON/MUTE
SELECT
OFF/ENTER
SELECT
keys
Function
Illustration
• Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.
• Mute the alarm: When the UPS is on battery mode, press and hold this button for at least
5 seconds to disable or enable the alarm system. Not applicable to situations when
ON/
warnings or errors occur.
Mute button
• Up key: Press this button to display previous selection in UPS settings mode.
• Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds to enter UPS
self-testing while in AC mode, ECO mode, or converter mode.
• Turn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS.
OFF/
UPS will be in standby mode under power normal or will transfer to bypass mode,
Enter button
if the bypass enable is set when this button is pressed.
• Confirm selection key: Press this button to confirm selection in UPS settings mode.
• Switch LCD message: Press this button to change the LCD message for input voltage,
input frequency, battery voltage, output voltage and output frequency. It will revert to
default display after 10 seconds of no input.
Select button
• Settings mode: Press and hold this button for 5 seconds to enter UPS settings mode when
UPS is in standby mode or bypass mode.
• Down key: Press this button to display next selection in UPS settings mode.
• Switch to bypass mode: When the main power is normal, press ON/Mute and select
ON/Mute +
buttons simultaneously for 5 seconds. Then UPS will enter bypass mode. This action will
Select button
be ineffective when the input voltage is out of acceptable range.
OFF/Enter +
• Switch LCD screen 90°: Press Off/Enter and select buttons simultaneously 5 second.
Select button
The UPS LCD screen will rotate 90°.
VAC
H
%
z
VDC
H