ABB PowerValue 11 RT G2 IN User Manual page 29

Hide thumbs Also See for PowerValue 11 RT G2 IN:
Table of Contents

Advertisement

U S E R M A N U A L
17: EPO logic setting
Interface
18: LCD display type
Interface
19: Audio alarm enable/disable
Interface
20: DC start enable/disable
Interface
21: Ambient temperature warning enable/disable
Interface
22: Automatic battery test
Interface
Settings
Set up the EPO function control logic.
AO: Active Open (Default). When AO is selected as EPO logic, it will activate EPO
function with Pin 1 and Pin 2 in open status.
AC: Active Close. When AC is selected as EPO logic, it will activate EPO function with
Pin 1 and Pin 2 in close status.
Settings
Set up LCD display type.
RAC: The LCD display type is rack (default).
TOE: The LCD display type is tower.
Settings
Set audio alarm
ENA: Audio alarm enable (default)
DIS: Audio alarm disable
Settings
Enable or disable DC start function.
ENA: DC start enable (default)
DIS: DC start disable
Settings
Enable or disable ambient temperature warning.
ENA: Ambient temperature warning enable (default)
DIS: Ambient temperature warning disable
Settings
Set up automatic battery test frequency.
The setting range is 0-31 days.(Default: 7 days)
29

Advertisement

Table of Contents
loading

Table of Contents