Ups Socket Output Connection - ABB PowerValue 11 RT G2 IN User Manual

Hide thumbs Also See for PowerValue 11 RT G2 IN:
Table of Contents

Advertisement

U S E R M A N U A L
10. Pass the output cable through the gland
assembly; use PVC single cord, 3G, 2.5 mm2,
double-insulated, rated 300 V (IEC 60227-1).
The overall diameter of the power supply cord
must be approximately 10.5 mm to allow
reliable clamping from cable gland, to prevent
failure from arcing and electric shock.
3.4.4-7
PVC single cord for Output wiring
11. Connect three wires according to the
polarities indicated on the terminal blocks.
Be sure to connect ground first.
3.4.4-8
Wires connection for Output wiring
12. Put the terminal cover back on the UPS by
fixing 4 screws.
3.4.4-9
Cover back
13. The UPS does not incorporate a disconnect
device, that must be part of the building
installation: UPS mains input shall be
protected by a 2-pole overcurrent protection
device according to IEC 60898-1 / IEC 60947-2
not exceeding 25 A.

3.4.5 UPS socket output connection

The output sockets and types of the UPS are
shown below.
Model No.
Output socket – India (pcs)
PowerValue 11 RT G2 1 kVA
4 x India 10A
PowerValue 11 RT G2 2 kVA
4 x India 10A
PowerValue 11 RT G2 3 kVA
2 x India 10A
There are two groups of output: P1 and P2
outlets. Backup time of each group can be set up
through LCD setting.