16
POWERVALUE 11 RT G2 IN — 1-3 KVA
WARNING!
1. The cover and cable gland must be installed
over input terminals and input cables to
prevent risk of electric shock during
standalone/tower use.
3.4.4-1
Terminal cover hole for Input wiring
2. Push in the hole of terminal cover.
3. Separate pressure dome and lock nut, assemble
the provided spare cable glands on the two
sides of terminal cover and screw it tightly.
3.4.4-2
Spare cable glands for Input wiring
4. Pass the input cable through the gland
assembly; use PVC single cord, 3G, 2.5 mm2,
double-insulated, rated 300 V (IEC 60227-1).
The overall diameter of the power supply cord
must be approximately 10.5 mm to allow
reliable clamping from cable gland, to prevent
failure from arcing and electric shock.
3.4.4-3
PVC single cord for Input wiring
The wiring installation shall be
performed by qualified personnel only.
5. Connect three wires according to the
polarities indicated on the terminal blocks.
Be sure to connect ground first.
6. Put the terminal cover back on the UPS by
fixing 4 screws.
3.4.4-4
Wires connection for Input wiring
7. The cover and cable gland must be installed
over output terminals and output cables to
prevent risk of electric shock during
standalone/tower use.
3.4.4-5
Terminal cover hole for Output wiring
8. Push in the hole of terminal cover.
9. Separate pressure dome and lock nut,
assemble the provided spare cable glands on
the two sides of terminal cover and screw it
tightly.
3.4.4-6
Spare cable glands for Output wiring