POWERVALUE 11 RT G2 IN — 1-3 KVA
08: Bypass voltage range setting
Interface
09: Bypass frequency range settings
Interface
Settings
Set the acceptable high voltage point and low voltage point for Bypass mode by
pressing the Down key or Up key
HLS: Bypass high voltage point
245-276: Sets the high voltage point in parameter 2 from 245 Vac to 276 Vac
(Default: 264 Vac)
LLS: Bypass low voltage point
120-215: Sets the low voltage point in parameter 2 from 120 Vac to 215 Vac
(Default: 184 Vac)
Settings
Set the acceptable high frequency point and low voltage point for Bypass mode by
pressing the Down key or Up key
HLS: Bypass high frequency point
51.0-54.0: Sets the high frequency point in parameter 2 from 51.0 Hz to 54.0 Hz for
50 Hz system. (Default: 54.0 Hz)
61.0-64.0: Sets the high frequency point in parameter 2 from 61.0 Hz to 64.0 Hz for
60 Hz system. (Default: 64.0 Hz)