06: ECO frequency range settings
Interface
07: Bypass enable/disable when UPS is off
Interface
Settings
Set the acceptable high frequency point and low frequency point for ECO mode by
pressing Down key or Up key
HLS: High loss frequency in ECO mode.
The setting range in parameter 2 is from 5% to 10% of the nominal voltage.
(Default: 5%)
LLS: Low loss frequency in ECO mode in.
The setting range in parameter 2 is from -5% to -10% of the nominal voltage.
(Default: -5%)
Settings
Enable or disable Bypass function. You may choose the following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)