ABB PowerValue 11 RT G2 IN User Manual page 28

Hide thumbs Also See for PowerValue 11 RT G2 IN:
Table of Contents

Advertisement

28
POWERVALUE 11 RT G2 IN — 1-3 KVA
12: Autonomy limitation settings
Interface
WARNING!
13: External battery Ah
Interface
14: External battery module numbers
Interface
15: Input dry contact
Interface
16: Output dry contact
Interface
Settings
Set up backup time on battery mode for output receptacles.
0-999: Sets the backup time in minutes from 0-999 for output receptacles on
battery mode
0: When setting as "0", the backup time will be only 10 seconds.
999: When setting as "999", the backup time setting will be disabled. (Default)
It is mandatory set both parameters #13 and #14 for the correct operation of the system.
Settings
Set up total capacity in Ah of an external third party battery pack [no standard ABB
External Battery Modules (EBM) are connected].
Allowed values are integer in the range of 7-999 (Ah). The default value is "20" (Ah).
Keep it as default if connecting to standard ABB External Battery Modules (EBM).
This setting will enable the UPS-model S to self-adjust the battery charger current,
up to max 6 A; for the UPS-model B the battery charger current will be maintained
at 1.5 A.
Settings
Set the total number of standard ABB External Battery Modules [no third party
external battery packs are connected]. Allowed values are integer in the range 0-9.
The default value is "0". Set it as "1" if third party external battery packs are
connected This setting will enable the UPS-model S to self-adjust the battery
charger current, up to max 6 A; for the UPS-model B the battery charger current
will be maintained at 1.5 A
Settings
Set up input dry contact. You may choose the following selections:
DIS: Disable the function (default)
TON: UPS Turn On
TOF: UPS Turn Off
MBS: Maintain Bypass
Settings
Set up output dry contact. You may choose the following selections:
SAL: Summary Alarm (default)
BTA: Battery Active
LBA: Low Battery
UPN: UPS Normal
BSA: Bypass Active