U S E R M A N U A L
10: Programmable outlets enable/disable
Interface
11: Programmable outlets setting
Interface
LLS: Bypass low frequency point
46.0-49.0: Sets the low frequency point in parameter 2 from 46.0 Hz to 49.0 Hz for
50 Hz system. (Default: 46.0 Hz)
56.0-59.0: Sets the low frequency point in parameter 2 from 56.0 Hz to 59.0 Hz for
60 Hz system. (Default: 56.0 Hz)
Settings
Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)
Settings
Set up P1 or P2 programmable outlets by pressing "up" or "down" key in
parameter 2.
P1: Set up P1 programmable outlets
P2: Set up P2 programmable outlets
After selecting P1 or P1, press "Enter" key to access backup time limits setting page.
At this time, it will still show "11" in parameter 1 and you may set up backup time
limits in parameter 2.
0-999: Setting the backup time limits in minutes from 0-999 for programmable
outlets P1 or P2 on battery mode. (Default: 999)
27