Important Information - EA Technology UltraTEV Monitor Operating Manual

Table of Contents

Advertisement

EA Technology
1

Important Information

UltraTEV Monitor
Care must be taken where work is performed in tight corners, where the
proximity of other earth planes will affect the reading.
maintain a distance of more than 30cm from metal work which runs
perpendicular to the sensor faceplate.
Strong electromagnetic fields from mobile phones, RF transmitters,
VDUs and un-screened electronics in the frequency range DC to 1GHz
can have an effect on the readings. A measure of local fields can be
obtained by holding the UltraTEV Monitor in free-air at least 1 metre
away from any conducting surface.
The UltraTEV Monitor must be used in accordance with local safety rules
and procedures.
The UltraTEV Monitor is designed for use at
The UltraTEV Monitor™ is designed and tested for indoor use only.
When testing electrical plant ensure that the metalwork is earthed before
applying the Nodes/Probes.
Maintain safety distances between structures at high voltage and the
UltraTEV Monitor and its operator at all times.
Do not operate the UltraTEV Monitor or its accessories in an explosive
atmosphere.
The UltraTEV Monitor contains no user serviceable parts, always return
to EA Technology or your local distributor for service and repair.
Do not hard wire the unit to the mains supply without providing a means
of emergency disconnection
In the event that the supplied wall plug is changed, EA Technology
assumes no legal responsibility for the safety of the instrument or persons
using the instrument.
EA Technology RFCTs are designed to be installed by suitably competent
operators on cable earth/ground straps which are suitably and efficiently
connected to earth/ground to maintain safety.
RFCTs, connecting leads and test equipment
against high voltage.
Operators must ensure that the cable earth/ground conductor is capable
of carrying the prospective earth/ground fault current for the time
required for protective devices to operate and without giving rise to
dangerous voltages or creating danger. The integrity of earth/ground
conductors and connections should be confirmed by the operator prior to
installation of the RFCT.
Operating Manual
TM
ground
do not
5
2178L014
If possible
potential only.
provide protection