Xantrex Freedom EX 4000 Owner's Manual page 53

Inverter/charger with 48vdc-to-12vdc converter
Hide thumbs Also See for Freedom EX 4000:
Table of Contents

Advertisement

Invert Sub-settings
Setting
Setting Name
Number
I1
Low Battery Cutout 
(LBCO)
I2
LBCO Hysteresis
I3
LBCO Delay
975-0999-01-01
Default
Range of Values
Value
44.0
36.0 to 50.0
6.0
0.0 to 10.0
10
0 to 600
Unit Step
V
0.1
Controls when the inverter turns off due to a low
battery voltage condition. The inverter will turn
off only after this level has been reached for the
period of time set by the LBCO Delay. This
setting is not temperature compensated.
NOTE: When battery voltage reaches below this
value, the battery must be recharged.
V
0.1
Determines the Low Battery Recovery Voltage
Level which is a summation of LBCO + LBCO
Hysteresis. The unit will resume operation if the
battery voltage exceeds the LBCO Recovery
Voltage Level.
s
5
Controls how long the inverter is allowed to
operate at or below the LBCO level before
turning off due to a low battery voltage
condition. When the range is from 1 to 20, the
timer setting value can be adjusted by 1-second
increments, then by 5-second increments above
20 seconds.
Adjusting Settings in Configuration Mode
Description
37