Feature
DC terminal opening for routing (–) negative DC
4
cable for inverting from or charging a 48V battery.
DC terminal opening for routing (+) positive DC
5
cable for inverting from or charging a 48V battery.
Single opening to two DC output terminals for
6
routing (–) negative and (+) positive DC cables for
12V DC loads. c Do not use for charging.
Grounding lug provides a ground path for the
7
Freedom EX 4000 chassis to the DC system ground.
See WARNING.
Cooling fans turn on when the internal temperature
8
reaches a set point temperature.
Mounting flanges on both sides allow you to mount
9
the inverter/charger/converter permanently on the
interior deck or on a wall.
975-0999-01-01
Description
WARNING
ELECTRICAL SHOCK HAZARD
Use a torque screwdriver to tighten the bolt on the DC
n
ground lug to a torque of 23 in-lb (2.6 N-m) of force.
Apply an anti-corrosion compound to the copper wire prior
n
to connecting to the DC ground lug.
Failure to follow these instructions can result in death, serious
injury, or equipment damage.
AC/DC Panel
9