Mechanical Specifications - Western Digital Ultrastar ScaleUp SE4U102 User Manual

Table of Contents

Advertisement

User Guide
Typical Power Consumption
PSU Connector Type
Inrush Current Maximum (per
Caution: The Ultrastar Data102 can only be plugged into high line (200-240 VAC) power. If
the unit is plugged into low line (110-127 VAC), the PSU will report a "Critical" state when status
pages are queried using SES. In this case, the enclosure will power up, but the drives will not.
The enclosure will remain in low-power mode.
1.6   Mechanical Specifications
Table 3: Mechanical Specifications
Specification
Enclosure Dimensions
Length of Enclosure w/
Required Rack Width
Required Rack Depth
Rack Units (U)
2.
Max and typical power consumption values represent the output power to the system. Input power will vary depending
on the PSU efficiency and load sharing between PSUs.
3.
Listed weight is for a dual-IOM enclosure, fully populated with 102 drives. It does not include the CMA, cable tray,
accessories, or packaging/shipping materials.
Specification
2
Input Voltage
PSU Efficiency
AC line inrush current shall not exceed 40A peak, for up to
PSU)
one-quarter of the AC cycle after which, the input current
should be no more than the specified maximum input current.
Non-Operational
Shock
10G, 0 - peak,11ms half sine;
3 positive and 3 negative
pulses in each axis Shock
Vibration
0.75G, 0 - peak swept sine;
5 -500Hz; 1 complete sweep
@ 1/2 octave per minute
Weight
CMA
450 mm (17.72 in.) minimum width, with 465 mm (18.31 in.) ±
1.5 mm nominal hole spacing. See EIA-310 Rack Standard.
1181-1197 mm (46.5in. - 47.13in.) of usable rack space, frame to frame
Value
~1300W
200-240 VAC
C14
80 PLUS Platinum
5G, 0 - peak, 11ms half sine; 3 positive
and 3 negative pulses in each axis-
minimum 6 seconds between shocks
to allow for write/read recovery
118.8 kg / 262 lbs.
W: 447 mm x L: 1048.5 mm x H: 175 mm
/ W: 17.67 in. x L: 41.28 in. x H: 6.89 in.
CMA Standard: 1183mm / 46.57in.
CMA Lite: 1148mm / 45.19in.
4U
1. Overview

1.6 Mechanical Specifications

Operational
0.10G, 0 - peak swept sine;
5 -500Hz; 1 complete sweep
@ 1/2 octave per minute
3
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ultrastar data1021ex1231