PuLEU
Pump too fast (low level)
LEUEL
Low level alarm in the level sensor
tEMNP
Overtemperature (t
bL0C
Pump blocked (no rotation)
CFA1L
Command connection interrupt
AL
1
Temperature signal of external Pt100 missing
AL
2
Temperature signal of analogue input missing
AL
3
Temperature signal of serial port missing
AL
4
Analogue module: Current input 1 interrupted
AL
5
Analogue module: Current input 2 interrupted
AL
6
Protection system: High bath level
AL
7
Error digital input (from V 1.30 on)
AL
8
Refill fail
Warnings from "Master-Display"
Message
WX
1
Overflow of CAN receipt
WX
2
Watchdog-Reset
WX
3
til-limitation active
WX
4
tih-limitation active
WX
5
Heatsink temperature
Software version of protection system too old
WX 11
Software version of operating system too old
WX 12
Software version of analogue Interface too old
WX 14
WX 15
Software version of RS-232 too old
Software version of contact I/0 module too old
WX 16
WX 17
Software version of Valve 0 too old
WX 18
Software version of Valve 1 too old
WX 19
Software version of Valve 2 too old
WX 20
Software version of Valve 3 too old
WX 21
Software version of Pump 0 too old
WX 22
Software version of Pump 1 too old
WX 23
Software version of Pump 2 too old
WX 24
Software version of Pump 3 too old
YACE0099 / 10/9/2018
Meaning
> tmax)
Meaning
Starting up
Warnings from "Safety system"
Message
WX101
Overflow of CAN receipt
WX102
Watchdog-Reset
WX103
Close to bath overflow
Bath level is approaching switch off level
WX104
or is out of optional range
WX105
Heater 1 break
WX106
Heater 2 break
WX107
Heater 3 break
WX110
Software version of control system too old
Software version of operating system too old
WX112
Software version of analogue interface too old
WX114
WX115
Software version of RS-232 too old
Software version of contact I/0 module too old
WX116
WX117
Software version of Valve 0 too old
WX118
Software version of Valve 1 too old
WX119
Software version of Valve 2 too old
WX120
Software version of Valve 3 too old
WX121
Software version of Pump 0 too old
WX122
Software version of Pump 1 too old
WX123
Software version of Pump 2 too old
WX124
Software version of Pump 3 too old
Meaning